HVAC FAULT CODES

RUUD ERROR CODES

Data Verified: January 2026

Professional diagnostic codes and troubleshooting steps.

Technical Note: RUUD systems are part of a shared manufacturing platform. These codes are identical for RHEEM.

Critical Severity
57

A2L Refrigerant Leak Detected

Troubleshooting Steps

  • A2L SAFETY: The system has detected a concentration of R-454B. Blower will run at high speed to disperse gas.
  • Immediately ventilate the indoor area and keep spark sources away.
  • Check the A2L sensor in the indoor coil cabinet for a trip status.
  • Use an A2L-compliant leak detector to find the source of the leak.
Source Reference Rheem Endeavor Service Manual
High Severity
15

Compressor Discharge Temperature Protection

Troubleshooting Steps

  • Check for low refrigerant charge (system is running too hot).
  • Verify the outdoor electronic expansion valve (EEV) is moving and not stuck.
  • Inspect the outdoor coil for heavy dirt or debris blockage.
Source Reference Rheem Endeavor Service Manual
Normal Severity
20

Outdoor Ambient Thermistor Failure

Troubleshooting Steps

  • Check the ambient sensor wiring for damage (common for weed-whacker damage).
  • Verify resistance: 10k Ohms at 77°F.
  • The system will default to a fixed ambient temperature until fixed.
Source Reference Rheem Endeavor Service Manual
High Severity
39

DC Fan Motor Fault

Troubleshooting Steps

  • Check for physical obstructions (ice, branches) in the fan blade.
  • Inspect the 5-pin wiring harness between the motor and the control board.
  • Measure DC voltage at the motor plug; if voltage is present but motor doesn't spin, replace motor.
Source Reference Rheem Endeavor Service Manual
Medium Severity
41

Compressor Discharge Thermistor Failure

Troubleshooting Steps

  • Inspect the sensor located on the compressor discharge line.
  • Verify the sensor has not slipped out of its thermal sleeve.
  • Check for a short or open circuit in the sensor lead.
Source Reference Rheem Endeavor Service Manual
Critical Severity
82

Compressor Over-Current Protection (Inverter)

Troubleshooting Steps

  • Check the compressor windings for a short to ground.
  • Verify the power supply voltage is not sagging under load.
  • Check for a locked rotor (seized compressor).
Source Reference Rheem Endeavor Service Manual
High Severity
93

Compressor Phase Loss / Start-up Failure

Troubleshooting Steps

  • Check the U, V, W wiring between the inverter and compressor.
  • Inspect the inverter board for visible burn marks or failed capacitors.
  • Verify the compressor resistance across all three pins is equal.
Source Reference Rheem Endeavor Service Manual
Critical Severity
26

Line and Neutral Reversed

Troubleshooting Steps

  • ELECTRICAL SAFETY: The furnace has detected that the hot and neutral wires are swapped.
  • Check the polarity at the service switch and the main breaker panel.
  • Verify the furnace is properly grounded (Common cause for false polarity trips).
Source Reference Rheem Endeavor Service Manual
High Severity
61

Blower Motor Fault (No Communication)

Troubleshooting Steps

  • Check the 16-pin or 4-pin harness to the variable speed blower motor.
  • Verify the motor is receiving high-voltage power.
  • Ensure the control board's blower relay is engaging.
Source Reference Rheem Endeavor Service Manual
Critical Severity
26

Line and Neutral Reversed

Troubleshooting Steps

  • ELECTRICAL SAFETY: The furnace has detected that the hot and neutral wires are swapped.
  • Check the polarity at the service switch and the main breaker panel.
  • Verify the furnace is properly grounded (Common cause for false polarity trips).
Source Reference Rheem Endeavor Service Manual
High Severity
61

Blower Motor Fault (No Communication)

Troubleshooting Steps

  • Check the 16-pin or 4-pin harness to the variable speed blower motor.
  • Verify the motor is receiving high-voltage power.
  • Ensure the control board's blower relay is engaging.
Source Reference Rheem Endeavor Service Manual
High Severity
41-13

Electronic Expansion Valve (EEV) Coil Fault

Troubleshooting Steps

  • Measure the resistance of the EEV motor coils (typically 40-50 ohms per phase).
  • Check the 6-pin EEV connector for moisture or corrosion.
  • Verify the EEV 'clicks' during the system power-up initialization sequence.
Source Reference Rheem Endeavor Service Manual
High Severity
10-15

High Pressure Switch Trip

Troubleshooting Steps

  • Check for a dirty outdoor coil or a failed outdoor fan motor.
  • Ensure the service valves are fully open.
  • Verify the system is not overcharged with refrigerant after a recent service.
Source Reference Rheem Endeavor Service Manual
High Severity
11

Failed Ignition (3 Retries)

Troubleshooting Steps

  • Verify the gas valve is in the 'ON' position and gas pressure is sufficient.
  • Check if the hot surface igniter is glowing orange during the start sequence.
  • Ensure the burner ports are not clogged with spider webs or rust.
Source Reference Rheem Diagnostic Codes
Critical Severity
33

Roll-Out Switch Open

Troubleshooting Steps

  • FIRE SAFETY: Flames have 'rolled out' of the burner box. Check for a cracked heat exchanger.
  • Inspect for a blocked flue or vent pipe preventing exhaust flow.
  • Check the physical rollout switch for a manual reset button (usually located near the burners).
Source Reference Rheem Diagnostic Codes