HVAC FAULT CODES

CARRIER ERROR CODES

Data Verified: January 2026

Professional diagnostic codes and troubleshooting steps.

Technical Note: CARRIER systems are part of a shared manufacturing platform. These codes are identical for BRYANT and PAYNE.

Normal Severity
12

Furnace - Blower on after Power-up

Troubleshooting Steps

  • Blower runs for 90 seconds if power is lost during a call for heat.
  • Check for recent power interruptions.
  • Verify thermostat settings.
Source Reference TIC 2019-0002
High Severity
13

Furnace – Limit Lockout

Troubleshooting Steps

  • Check for dirty air filters or blocked return air vents.
  • Verify blower motor operation and speed settings.
  • Inspect high-limit switch for proper operation.
Source Reference TIC 2019-0002
High Severity
14

Furnace – Ignition Lockout

Troubleshooting Steps

  • Check gas valve and igniter resistance.
  • Verify flame sensor cleanliness and positioning.
  • Ensure gas supply is active and unobstructed.
Source Reference TIC 2019-0002
High Severity
15

Furnace – Blower Lockout

Troubleshooting Steps

  • Check blower motor wiring and capacitor.
  • Verify motor is not seized or overheating.
  • Inspect control board for blower relay failure.
Source Reference TIC 2019-0002
High Severity
22

Furnace – Flame Sense Error

Troubleshooting Steps

  • Clean the flame sensor with light abrasive (steel wool).
  • Check for proper grounding of the burner assembly.
  • Verify flame is making direct contact with the sensor rod.
Source Reference TIC 2019-0002
Medium Severity
23

Furnace – LPS or HPS Fault

Troubleshooting Steps

  • Inspect Low Pressure Switch (LPS) and High Pressure Switch (HPS).
  • Check for blocked intake or exhaust venting.
  • Verify pressure switch tubing is clear of moisture or kinks.
Source Reference TIC 2019-0002
Critical Severity
24

Secondary Voltage Fuse Is Open

Troubleshooting Steps

  • Check the 3-amp fuse on the control board; replace if blown.
  • Inspect for a short circuit in the low-voltage thermostat wiring (check the outdoor unit contactor).
  • Verify no wires are pinched or touching the furnace chassis.
Source Reference TIC 2019-0002
High Severity
25

Invalid Model Selection

Troubleshooting Steps

  • Check that the model plug on the control board is present and correct.
  • Ensure the control board is the correct replacement part for this specific model.
  • Power cycle the system to see if the board re-recognizes the unit.
Source Reference TIC 2019-0002
High Severity
31

Pressure Switch Did Not Close or Reopened

Troubleshooting Steps

  • Check for a blocked flue vent, excessive wind, or disconnected pressure tubing.
  • Inspect the condensate line for clogs (common in high-efficiency units).
  • Verify the inducer motor is running at the correct speed.
Source Reference TIC 2019-0002
Medium Severity
32

Low-Heat Pressure Switch Did Not Close

Troubleshooting Steps

  • Check for restricted combustion air supply or plugged condensate drain.
  • Inspect pressure switch wiring and verify tubing is not sagging or holding water.
  • Verify low inlet gas pressure if using a Low Gas Pressure Switch (LGPS).
Source Reference TIC 2019-0002
High Severity
33

Limit Circuit Fault / Open Limit Switch

Troubleshooting Steps

  • Check for restricted airflow caused by a dirty filter or closed registers.
  • Inspect the blower motor to ensure it is moving enough air.
  • Check the limit switch and limit gasket for damage.
Source Reference TIC 2019-0002
High Severity
34

Ignition Proving Fault

Troubleshooting Steps

  • Clean the flame sensor with fine steel wool or a Scotch-Brite pad.
  • Check for proper grounding of the burner assembly and control board.
  • Verify the Hot Surface Ignitor (HSI) is glowing and positioned correctly.
Source Reference TIC 2019-0002
High Severity
41

Blower Motor Outside Valid Speed Range

Troubleshooting Steps

  • Check for physical obstructions in the blower wheel.
  • Verify the blower motor wiring harness is secure.
  • Check for high static pressure in the ductwork.
Source Reference TIC 2019-0002
High Severity
42

Inducer Motor Fault

Troubleshooting Steps

  • Check for a faulty inducer motor or a blocked vent pipe.
  • Inspect wiring connections between the inducer and the control board.
  • Verify the inducer motor capacitor is functional (if applicable).
Source Reference TIC 2019-0002
High Severity
44

Blower Motor Fault

Troubleshooting Steps

  • Inspect the blower motor for failure or loose wiring.
  • Check the control board for any burnt relays related to the blower.
  • Verify line voltage is reaching the motor.
Source Reference TIC 2019-0002
Critical Severity
45

Control Circuitry Lockout

Troubleshooting Steps

  • Reset power to clear the lockout; if it repeats, the control board likely needs replacement.
  • Check for a stuck-open gas valve relay on the board.
  • Verify there are no software check errors or flame sense circuit failures.
Source Reference TIC 2019-0002
Medium Severity
51

Blower Motor Communication Fault

Troubleshooting Steps

  • Check the communication wiring between the variable-speed blower and the control board.
  • Verify the motor has proper power and ground.
  • Replace the blower motor's control module if communication cannot be restored.
Source Reference TIC 2019-0002
High Severity
53

Outdoor Unit Communication Fault

Troubleshooting Steps

  • Check ABCD wiring between the indoor and outdoor control boards.
  • Verify the outdoor unit has 240V power and the transformer is outputting 24V.
  • Inspect for blown fuses on the outdoor inverter or start-up board.
Source Reference TIC 2019-0002
Medium Severity
54

Outdoor Inverter / Controller Board Temperature Sensor Fault

Troubleshooting Steps

  • Check the thermistor resistance on the inverter heat sink.
  • Ensure the heat sink is clear of debris and the cooling fan is operational.
  • Replace the inverter board if the sensor is integrated and failing.
Source Reference TIC 2019-0002
Normal Severity
55

Outdoor Ambient Temperature Sensor Fault

Troubleshooting Steps

  • Check the ambient thermistor for damage or disconnection.
  • Verify resistance against the manufacturer’s temperature chart.
  • System may default to 'backup' modes until the sensor is replaced.
Source Reference TIC 2019-0002
Medium Severity
56

Outdoor Evaporator / Coil Temperature Sensor Fault

Troubleshooting Steps

  • Inspect the coil sensor for proper mounting on the liquid line.
  • Check for corrosion at the plug-in connector on the board.
  • Replace sensor if resistance is open or shorted.
Source Reference TIC 2019-0002
Critical Severity
57

A2L Refrigerant Leak Detected (2026 Standard) / Pressure Switch Error

Troubleshooting Steps

  • A2L SAFETY: Evacuate the premises and ensure the indoor blower is running to ventilate gas.
  • Check A2L mitigation sensor for a 'Leak' trip status.
  • Check high/low pressure switch circuit if unit is a legacy R-410A model.
Source Reference TIC 2019-0002 / 2026 Truth Table
High Severity
58

Outdoor Discharge Temperature Sensor Fault

Troubleshooting Steps

  • Check the discharge line thermistor located on the compressor pipe.
  • Ensure the sensor hasn't slipped out of its thermal well/clip.
  • Verify refrigerant charge; high discharge temps can sometimes trigger sensor errors.
Source Reference TIC 2019-0002
High Severity
71

Compressor Thermal Cutout

Troubleshooting Steps

  • Allow compressor to cool for 2 hours; check for internal overload trip.
  • Verify outdoor fan motor is running and coil is clean.
  • Check for low refrigerant charge or non-condensables in the system.
Source Reference TIC 2019-0002
High Severity
72

Compressor Low Pressure Dropout

Troubleshooting Steps

  • Check for a refrigerant leak or a stuck-closed Electronic Expansion Valve (EEV).
  • Verify indoor airflow (dirty filter or blower failure).
  • Inspect the Low Pressure Switch (LPS) wiring.
Source Reference TIC 2019-0002
High Severity
73

Compressor High Pressure Dropout

Troubleshooting Steps

  • Check for a dirty outdoor coil or failed outdoor fan motor.
  • Verify the system is not overcharged with refrigerant.
  • Check for closed service valves or restrictions in the liquid line.
Source Reference TIC 2019-0002
Critical Severity
81

VFD (Variable Frequency Drive) Inverter Lockout

Troubleshooting Steps

  • Check the inverter power module for a short circuit.
  • Inspect the compressor windings for a ground fault.
  • Verify incoming line voltage is stable (within +/- 10%).
Source Reference TIC 2019-0002
Medium Severity
191

Wall Control - UI Error / Communication Lost

Troubleshooting Steps

  • Reset the Wall Control (Thermostat) by pulling it off the subbase for 10 seconds.
  • Check for a loose 'Green' or 'White' wire on the ABCD bus.
  • Update Wall Control firmware if available.
Source Reference TIC 2019-0002
Medium Severity
192

SAM – SAM Radio Test Failed

Troubleshooting Steps

  • Ensure the System Access Module (SAM) antenna is properly connected and not obstructed by metal.
  • Check for local 2.4GHz interference from other wireless devices.
  • Power cycle the SAM and re-initiate the radio test via the Wall Control.
Source Reference TIC 2019-0002
Medium Severity
193

SAM – SAM Profile Failed

Troubleshooting Steps

  • The SAM failed to download the equipment profile; check internet connectivity.
  • Verify that the SAM is registered correctly on the manufacturer's cloud portal.
  • Perform a factory reset on the SAM and re-bind it to the Wall Control.
Source Reference TIC 2019-0002
High Severity
194

Wall Control – Possible Frozen Coil

Troubleshooting Steps

  • Check for restricted airflow: replace dirty air filters and open all supply registers.
  • Inspect the indoor blower motor for proper operation.
  • Verify refrigerant charge levels; a low charge can cause the evaporator coil to freeze.
Source Reference TIC 2019-0002
Normal Severity
195

Wall Control – Utility Curtailment Event

Troubleshooting Steps

  • Informational only: The local utility company has remotely limited HVAC usage during peak demand.
  • System will return to normal operation once the utility event concludes.
  • Check settings in the Wall Control to opt-out of future events if desired.
Source Reference TIC 2019-0002
Medium Severity
196

Wall Control – Auxiliary Input (G) Shutdown

Troubleshooting Steps

  • Check the 'G' terminal input on the indoor control board for an active 24V signal.
  • This is often wired to a float switch or fire alarm; check for a tripped condensate pan switch.
  • Clear any water from the secondary drain pan if a float switch is present.
Source Reference TIC 2019-0002
High Severity
210

Wall Control – Excessive Static Pressure Encountered

Troubleshooting Steps

  • The system detected static pressure above 1.0" WC. Check for highly restrictive 'high-MERV' filters.
  • Inspect ductwork for collapsed sections, closed dampers, or undersized returns.
  • Verify that the total number of open registers is sufficient for the system's tonnage.
Source Reference TIC 2019-0002
Medium Severity
211

Wall Control – Zone 1 Airflow Limited / Stage Down

Troubleshooting Steps

  • The system has reduced capacity to protect itself because Zone 1 cannot handle the required airflow.
  • Check the Zone 1 damper for proper opening and verify the duct size for that zone.
  • Ensure the Zone 1 temperature sensor is not located near a heat source causing false calls.
Source Reference TIC 2019-0002
Medium Severity
212

Wall Control – Zone 2 Airflow Limited / Stage Down

Troubleshooting Steps

  • Check Zone 2 dampers and ductwork for restrictions.
  • Verify that the Zone 2 bypass damper (if used) is weighted correctly.
  • Ensure registers in Zone 2 are not blocked by furniture.
Source Reference TIC 2019-0002
High Severity
91

System Communication Fault (ABCD Bus)

Troubleshooting Steps

  • Check for a cross-wired ABCD connector (e.g., A wired to B).
  • Inspect for a loose data wire at the Indoor Control Board or Wall Control.
  • Ensure the communication wires are shielded or kept away from high-voltage lines.
Source Reference TIC 2019-0002
High Severity
178

VFD Inverter – Heat Sink Over-Temperature

Troubleshooting Steps

  • Verify the outdoor unit inverter cooling fan is rotating and clear of debris.
  • Inspect the thermal paste between the power module and the heat sink.
  • Check for high ambient conditions or direct sunlight heating the control box.
Source Reference TIC 2019-0002
Critical Severity
171

VFD Inverter – DC Bus Over-Voltage

Troubleshooting Steps

  • Check incoming line voltage; it may be exceeding the 253V limit.
  • Verify the compressor is not back-feeding voltage during a rapid shutdown.
  • Inspect the inverter board for damaged capacitors or surge protection components.
Source Reference TIC 2019-0002
High Severity
173

VFD Inverter – Compressor Phase Current Imbalance

Troubleshooting Steps

  • Measure the resistance of each compressor winding (U-V, V-W, W-U); they must be nearly identical.
  • Check for loose or corroded terminal connections at the compressor plug.
  • If windings are balanced, the inverter power module (IPM) is likely failing.
Source Reference TIC 2019-0002
High Severity
16

Communication Error (Indoor or Outdoor Unit)

Troubleshooting Steps

  • Check ABCD wiring for a short or break in the data lines.
  • Verify that the model plug is securely installed on the control board.
  • Inspect for interference from nearby high-voltage lines running parallel to the bus.
Source Reference TIC 2019-0002
Critical Severity
21

Gas Heat Lockout / Invalid Model Plug

Troubleshooting Steps

  • The control board does not recognize the furnace model. Check if the model plug is missing.
  • If a new board was installed, ensure it is the correct part number for this BTU rating.
  • Power cycle the unit to see if the board re-recognizes the model configuration.
Source Reference TIC 2019-0002
High Severity
35

Modulating Gas Valve Communication Fault

Troubleshooting Steps

  • Check the wiring harness between the main board and the modulating gas valve.
  • Verify the gas valve is receiving 24V power.
  • If wiring is intact, the modulating solenoid or the valve’s logic board may have failed.
Source Reference TIC 2019-0002